S0005391
Generator set,diesel,water cool,10kVA**
Diesel driven generator set, water cooled, skid mounted, capable of delivering up to 10 kVA at 1500 rpm.
Indicative Price USD 5,750.30
General Description:
Diesel driven generator set, water cooled, and skid mounted, capable of delivering up to 10kVA at 1500rpm
Technical Specifications:
General:
A complete diesel generator set including the diesel engine, alternator, control panel, automatic starting equipment, fuel tank and all other accessories for autonomous operation
Rated Power:
10kVA, 24kW, Power factor (Cos. phi = 0.8), 400/230V, 3-phase, 50Hz at NTP (Normal Temperature and Pressure)
The use of the generator as prime or stand-by should be clearly stated by the country office when the set is requested
Engine:
Heavy duty diesel engine, with the following characteristics:
Water-cooled with fresh water loop and tropical radiator
Synchronous speed: Up to 1500rpm
Mechanical speed governor
Heavy duty air cartridge filter
Cartridge oil filter
External fuel filter
Industrial silencer
Exhaust with suitable flexible piping
Automatic electric starter including batteries leads and automatic battery charging equipment
Fuel Tank:
Fuel tank of suitable construction with capacity sufficient to run the generator set continuously for 8 hours at the rated capacity
Suitable piping should be provided for connecting the tank to the engine as well as for filling the tank
Fuel level indicator should be placed conveniently on the panel board
Alternator:
Synchronous and brushless
Automatic fast voltage regulator, maintaining the output within 2 % under normal conditions
Screen protected
CEE Sockets: one 3 pole and one 5 pole
Panel Board:
Made of steel sheets of appropriate thickness subjected to anti-oxidizing treatment and covered with epoxy resin with suitable protection factor
The panel board comprises:
Automatic main circuit breaker
Change over switch with positions for:"MAINS" - "OFF" - "GENERATOR".
Key to start and stop the unit
Emergency stop button
Set-point for speed/governor control
Set-point for voltage control
Meters for volts (with selector switch to show phases to zero, and phase to phase voltages), amperes (three meters or with selector switch to show current in all three phases), frequency, running hours counter
Acoustic and visible alarms for critical parameters including high engine temperature low oil pressure and low fuel should be provided
Protection:
The generator set should be equipped with automatic shutdown equipment if fatal parameters are exceeded including low oil pressure, high engine temperature and over-speed
Mounting:
The engine and the alternator should be connected with a heavy-duty elastic coupling and should be mounted on a common rigid base frame with anti-vibration dampers and lifting eyes flexible for transportation
Engine, alternator and panel should be one integrated unit mounted on skids
Connection to ground:
The generator is supplied with connection to ground system comprising low resistance rod(s), terminals, cables, etc
Environmental conditions:
The rated power of the generator is based on the following environmental conditions:
(The country office should provide the actual local conditions to enable the calculation of de-rating that fits those local conditions.)
Altitude at 150m above sea level
Average yearly temperature 30°C
Average 24 hours temperature 40°C
Minimum temperature -10°C
Maximum operating temperature 55°C
Dust storms are expected
Accessories:
The following accessories are supplied with the generating set:
Operation and maintenance manuals (full workshop documentation for both engine and alternator), spare parts catalogues, drawings and information concerning the foundation, erection requirements, electrical connections to load and earth, etc. All in English (other languages could be provided as an option against additional cost).
Engine coolant/antifreeze liquid for the first installation
Tools kit including pipe spanners for injectors, etc
Spare parts for 2000 hours of operation within two years (including oil and air filter cartridges and at least two full sets of v-belts and a full set of cylinder head gaskets).
A full set of replacement switches/sensors for detection of fatal parameters (low oil pressure, high engine temperature, belt failure, etc)
Options:
The following are available as optional items
Each one could be specifically requested by the country office if needed:
Automatic Mains Failure (AMF)
The generator set mounted in a sound attenuated and weather protective canopy, to reduce the noise level down to 70 dB(A) at a distance of 7 metres
Trailer mounting
Manuals in languages other than English
Packaging and labelling:
The unit is packed in strong sea-worthy wooden box
Transport of generator as per Material Safety Data Sheet:
UN number 3166
Danger class 9
Packing instructions 900
Proper shipping name:
Engines, internal combustion
Transport of battery as per Material Safety Data Sheet:
UN number 2794
Danger class 8
Packing group
Proper shipping name: Battery, wet, filled with acid
Weight/Volume/Dimensions:
Estimated weight: 308kg
Estimated volume: 0.89cbm
Instructions for use:
For civil infrastructure power requirements such as hospitals, water pumping and treatment plants, etc
Related Products