S0005395
Generator set,diesel,air cooled,8kVA **
Diesel driven generator set, air cooled, skid mounted, with an output of
8 kVA at 1500 rpm.
Indicative Price USD 9,600.00
General Description:
Diesel driven generator set, air cooled and skid mounted, with an output of 8kVA at 1500rpm
Technical Specifications:
General:
A complete diesel generator set including the diesel engine, alternator, control panel, automatic starting equipment, fuel tank and all other accessories for autonomous operation
Rated Power:
8kVA, 6.4kW, Power factor (Cos. phi = 0.8), 400/230V, 3-phase, 50Hz at NTP (Normal Temperature and Pressure)
The use of the generator as prime or stand-by should be clearly stated by the country office when the set is requested
Engine:
Heavy duty diesel engine, with the following characteristics:
Air cooled
Synchronous speed: up to 1500rpm
Mechanical speed governor
Heavy duty air cartridge filter
Cartridge oil filter
External fuel filter
Residential silencer
Exhaust with suitable flexible piping
Electric starter including batteries, leads and automatic battery charging equipment
Fuel Tank:
Fuel tank of suitable construction with capacity sufficient to run the generator set continuously for 8 hours at the rated capacity
The tank is provided with suitable piping for connecting it to the engine as well as for filling the tank
Fuel level indicator placed conveniently on the panel board
Alternator:
Synchronous, air cooled and brushless
Automatic fast voltage regulator, maintaining the output within 2 % under normal conditions
Screen protected
CEE Sockets: one 3 pole and one 5 pole
Panel board:
Made of steel sheets of appropriate thickness subjected to anti-oxidizing treatment and covered with epoxy resin with suitable protection factor
The panel board comprises the following:
Automatic main circuit breaker
Change over switch with positions for: MAINS- OFF- GENERATOR
Key to start and stop the unit
Emergency stop button
Set-point for speed/governor control
Set-point for voltage control
Meters for: Volts (with selector switch to show phases to zero and phase to phase voltages), amperes (three metres or with selector switch to show current in all three phases), frequency, running hours counter
Warning system for electrical and mechanical alarms
Protection:
The generator set should be equipped with automatic shutdown equipment if fatal parameters are exceeded including low oil pressure, high engine temperature and belt failure (if applicable)
Mounting:
The engine and the alternator should be connected with a heavy-duty elastic coupling and should be mounted on a common rigid base frame with anti-vibration dampers and lifting eyes flexible for transportation
Engine, alternator, fuel tank and panel should be one integrated unit mounted on skids
Connection to ground:
The generator is supplied with connection to ground system comprising low resistance rod(s), terminals, cables, etc
Environmental conditions:
The rated power of the generator is based on the following environmental conditions:
(The country office should provide the actual local conditions to enable the calculation of de-rating that fits those local conditions)
Altitude: at 150m above sea level
Average yearly temperature 30°C
Average 24 hours temperature 40°C
Minimum temperature -10°C
Maximum operating temperature 55°C
Dust storms are expected
Accessories:
The following accessories are supplied with the generating set:
Operation and maintenance manuals (full workshop documentation for both engine and alternator), spare parts catalogues, drawings and information concerning the foundation, erection requirements, electrical connections to load and earth, etc. all in English (other languages can be provided as an option against additional cost)
Engine coolant/antifreeze liquid for the first installation
Tools kit including pipe spanners for injectors, etc.
Spare parts for 2000 hours of operation within two years (including oil and air filter cartridges and at least two full sets of v-belts and a full set of cylinder head gaskets)
A full set of replacement switches/sensors for detection of fatal parameters (low oil pressure, high engine temperature, belt failure, etc)
Transport and storage:
Dangerous good: Hazardous Material - Transport Certification required
Transport of generator as per Material Safety Data Sheet:
UN number 3166
Danger class 9
Packing instr. 900
Proper shipping name: Engines, internal combustion
Transport of battery as per Material Safety Data Sheet:
UN number 2794
Danger class 8
Packing group
Proper shipping name: Battery, wet, filled with acid
Packaging: The set is packed in a strong sea worthy box
Storage: Do not store unprotected from rain and sun. After extended storage period, undergo maintenance before starting the engine
Instruction for use:
The generator set is used as an electrical power supply for light loads such as lighting and other ordinary office and household needs.
Regularly maintain the engine according to the manual (On the SD Intranet a sample template is posted to assist with the maintenance of the engine). See the generator maintenance sheet via the following link:
http://danaapps01.unicef.org/Denmark/DO/daniclguide.nsf/Pg/h0103
Precondition for utilisation:
Maintain a record sheet for the used hours
Prepare ventilated and covered room with noise reducer
Prepare the room with a covered outlet for the exhaust pipe
Alternative if the item is not available:
S1800342 Generator Set, Diesel, Portable, 8KVA**
S0005390 Generator Set, Diesel, Water Cooled, 8KVA**
S0005407 Generator Set, Diesel, Air Cooled, 10KVA**
S0005391 Generator Set, Diesel, Water Cooled, 10KVA**
Complementary Requirements, to be ordered separately:
Automatic Mains Failure (AMF)
The generator set mounted in a sound attenuated and weather protective canopy, to reduce the noise level down to 70dB (A) at a distance of 7 metres.
Commissioning and training of local personnel
A recommended program for the training could be provided
Recoil starting instead of the electric starting
Trailer mounting
Manuals in languages other than English
2 x 10 metres of power cable, 32Amp, 3-core, complete with socket and plugs
2 x 25 metres of distribution cables, 10Amp, 3-core, on cable reel
2 x 25 metres of distribution cable, 6Amp, 3-core, on cable reel
2 x distribution panel, 63Amp, with European CEE sockets type for outdoor use
2 x set of three-pin socket and plug
Contingency stock of fuel (200l) – if drum or containers need to be sealed
In order to measure consumption, manual pump with counter is recommended, made out of anti-static material
Emergency scenarios
All emergencies
Context in which item is mainly used:
Do not overcharge the generator and do not connect air-conditioning units to this generator.
Dangerous/Hazardous Material
The Sealed lead Batteries are not subject to dangerous goods transport regulations. Refer to MSDS Sheet.
Related Products